ARTESYN CPS250-M SERIES 250 Watt AC-DC Power Supplies Advanced Energy s Artesyn CPS250-M series of single DATA SHEET output open-frame AC-DC power supplies are offered in 12 V, 24 V, or 48 V outputs with +10% Trim range. Each power Total Power: supply comes with a 12 V fan output. All models feature ITE 250 Watts and medical safety approvals and accept a universal input of 90264 Vac. Depending on operating conditions, its 2 Input Voltage: x 4 x 1.29 compact and high density design delivers up to 90 - 264 V 155 watts of output power with free air convection cooling of Outputs: and up to 250 watts with 300 LFM of forced air. These power Single supplies are ideal for light industrial systems as well as for medical applications. SPECIAL FEATURES SAFETY Designed for forced air and natural EN 62368-1 / 60601-1 convection cooling UL/CSA 62368-1 / 60601-1 Medical and ITE safety approvals, 2x CSA MOPP CE LVD Mark Dual fused CCC Type BF ready ** CPS250-M tested according to the Active Power Factor Correction, medical standard IEC 60601-1-2 4th 61000-3-2 compliant Edition. Built-in Class B EMI filter Less than 1U high LPX100 enclosure kit available <500 mW no-load power consumption Compact size: 2 x 4 x 1.3 For use in Class I or Class II applications Three-year warranty (consult factory for extended terms) 2020 Advanced Energy Industries, Inc.CPS250-M SERIES ELECTRICAL SPECIFICATIONS Input Input voltage ra nge 90 - 264 Vrms Frequency 47 - 63 Hz (360 - 440 Hz with higher leakage) Inrush current 70 Apk, < 1 ms, cold start Efficiency 93% typical Leakage current Specified for medical approvals No load power < 500 mW Output Maximum power 250 W, forced-air cooling 155 W, free-air natural convection Adjustment range -0% / +10% Holdup time 10 ms 225 W Fan output 12 V 500 mA Standby output 5 V 100 mA (For CPS253-M1 only) Control and Protection Remote On/Off For CPS253-M1 only DC OK For CPS253-M1 only Overvoltage protection Latching/AC Recycle required to restart PSU Overcurrent protection Auto-recovery Short circuit protection Auto-recovery (impedance <50 mOhm Overtemperature protection Auto-recovery with hysteresis ENVIRONMENTAL SPECIFICATIONS Operating temperature -20 C to +70 C (derate at 50 C), startup at -40 C Storage temperature -40 C to +85 C Operating humidity 5% to 90% (non-condensing) Non-operating humidity 5% to 95% (non-condensing) Maximum altitude 5000 m (3000 m for medical), derating may apply 2 advancedenergy.com