D1U54P-W-1200-12-HxxPC Series 54mm 1U Front End AC-DC Power Supply Converter www.murata-ps.com PRODUCT OVERVIEW The D1U54P-W-1200-12-HxxPC series are 80 PLUS Platinum ef ciency 1200 watt, power factor corrected front end supplies with a 12V main output and a 3.3V (3A) or 5V (3A) standby. They have active current sharing and up to 8 supplies may be operated in parallel. The supplies may be hot plugged, they recover from overtemperature faults, and have status LEDs on their front panel in addition to logic and PMBus status signals. Their low pro le 1U package and >28W/cubic inch power density make them ideal for delivering reliable, ef cient power to servers, workstations, storage systems and other 12V distributed power systems. ORDERING GUIDE Power Output Power Output Main Standby Part Number Air ow High Line AC Low Line AC Output Output D1U54P-W-1200-12-HC4PC 3.3Vdc Back to front D1U54P-W-1200-12-HA4PC 5Vdc FEATURES 1200W 1100W 12Vdc D1U54P-W-1200-12-HC3PC 3.3Vdc 1200W output power Front to back D1U54P-W-1200-12-HA3PC 5Vdc 80 PLUS Platinum ef ciency 1 Refer to page 7 for alternate input connector (HxxxPTC). 2 The HCxPC variants are certi ed for compliance to 80 PLUS Platinum ef ciency requirements. 12V main output 3.3V and 5V standby output INPUT CHARACTERISTICS Parameter Conditions Min. Nom. Max. Units 1U height: 2.15 x 12.65 x 1.57 Input Voltage Operating Range 90 115/230 264 Vac 28 Watts per cubic inch density Input Frequency 47 50/60 63 Hz Turn-on Input Voltage Ramp up 80 85 89 N+1 redundancy capable, Vac Turn-off Input Voltage Ramp down 65 73 78 including hot plugging (up to 8 in parallel) Maximum current at Vin = 100Vac 1100W 12 Arms Active current sharing on 12V main output Inrush Current Cold start between 0 to 200msec 25 Apk ORing FET Power Factor At 230Vac, full load 0.99 20% load 90 Overvoltage, overcurrent, Ef ciency (230Vac) excluding fan load 50% load 94 % overtemperature protection 100% load 91 Internal cooling fan (variable speed) OUTPUT VOLTAGE CHARACTERISTICS PMBus / IC interface with status indicators Nominal RoHS compliant Output Parameter Conditions Min. Typ. Max. Units Voltage Two-year warranty Nominal Output Voltage 12 Vdc Output Set Point Accuracy 50% load Tamb =25C -0.5 +0.5 % Line and Load Regulation -1.0 +1.0 3 12V Ripple Voltage & Noise 20MHz Bandwidth 150 mV p-p Output Current (230Vac) 5 100 A Output Current (120Vac) 5 90 Load Capacitance 0 30,000 F Nominal Output Voltage 3.3 Vdc Line and Load Regulation 3.14 3.46 3 3.3VSB Ripple Voltage & Noise 20MHz Bandwidth 75 mV p-p Output Current 3 A Load Capacitance 1000 F Nominal Output Voltage 5.0 www.murata-ps.com/en/3d/acdc.html Vdc Line and Load Regulation 4.76 5.24 www.murata-ps.com/en/3d/acdc.html 3 5VSB Ripple Voltage & Noise 20MHz Bandwidth 75 mV p-p www.murata-ps.com/en/3d/acdc.html Output Current 0 3 A www.murata-ps.com/en/3d/acdc.html Load Capacitance 0 1000 F www.murata-ps.com/en/3d/acdc.html 3 www.murata-ps.com/en/3d/acdc.html Ripple and noise are measured with 0.1 F of ceramic capacitance and 10 F of tantalum capacitance on each of the power supply outputs. A short coaxial cable with 50 scope termination is used. Available now at www.murata-ps.com/en/3d/acdc.html PM CB Test Certi cate and Test Report For full details go to www.murata-ps.com/rohs www.murata-ps.com/support D1U54P-W-1200-12-HxxPC.A09 Page 1 of 8D1U54P-W-1200-12-HxxPC Series 54mm 1U Front End AC-DC Power Supply Converter OUTPUT CHARACTERISTICS Parameter Conditions Min. Typ. Max. Units Startup Time AC ramp up 3 s 12V, 50% load step, 1A/s di/dt 600 Transient Response mV 3.3VSB, 50% load step, 1A/s di/dt 165 Current sharing accuracy (up to 8 in parallel) At 100% load 7 % Hot Swap Transients All outputs remain in regulation 5 % Holdup Time 100% load 12 ms ENVIRONMENTAL CHARACTERISTICS Parameter Conditions Min. Typ. Max. Units Storage Temperature Range -40 70 C Operating Temperature Range 060 Operating Humidity Noncondensing 5 90 % Storage Humidity 595 Altitude (without derating at 40C) 3000 m Shock 30G non operating Sine sweep 5-150Hz, 2G Operational Vibration random vibration, 5-500Hz, 1.11G MTBF Per Telcordia SR-332 M1C1 40C 529K hrs CAN/CSA C22.2 No 60950-1-07, Am.1:2011, Am2:2014 UL 60950-1-2014, 2nd Ed. IEC60950-1:2005 (2nd ED.)+A1:2009+A2:2013 Safety Approval Standards EN60950-1:2006+A11+A1+A12+A2 CCC GB4943.1-2011 BSMI CN214336-1 Input Fuse Power Supply has internal 15A/250V fast blow fuse on the AC line input Weight 3.15 lbs (1.43 kg) PROTECTION CHARACTERISTICS Output Parameter Conditions Min. Typ. Max. Units Voltage Overtemperature (intake) Autorestart 70 80 C Overvoltage Latching 13 14 V 12V Overcurrent At 220Vac Hiccup 105 120 A Overcurrent At 110Vac Hiccup 99 117 Overvoltage Latching 3.6 4.0 V 3.3VSB Overcurrent Hiccup 3.3 4.5 A Overvoltage Latching 5.4 6.0 V 5VSB Overcurrent Hiccup 3.3 4.5 A ISOLATION CHARACTERISTICS Parameter Conditions Min. Typ. Max. Units Input to Output - Reinforced 3000 Vrms Insulation Safety Rating / Test Voltage Input to Chassis - Basic 1500 Vrms Isolation Output to Chassis 500 Vdc www.murata-ps.com/support D1U54P-W-1200-12-HxxPC.A09 Page 2 of 8