Highlights
3.2-3.8kW Single-Phase ATS/Metered PDU,
Single phase 16/20A 200-240V
200-240V (8 C13 & 2 C19), 2 C20, 12ft Cord, 1U
Auto Transfer Switch / ATS PDU
Rack-Mount, TAA
Enables redundant-power option
for single-corded network devices
MODEL NUMBER: PDUMH20HVAT
Separate primary & secondary
inputs connect to any two
compatible power sources
1U horizontal rackmount; 2 C20
inputs; 8 C13 and 2 C19 outlets
Two digit visual current meter;
Upgrade options available
Federal Trade Agreements Act /
TAA Compliant for GSA
Schedule purchases
Package Includes
Metered PDU with ATS Support
User manual with warranty
information
Description
Tripp Lite Metered ATS / Auto Transfer Switch provides a redundant power option for single-corded network devices. Dual input cords support separate
connection to PRIMARY and SECONDARY power sources. The ATS will normally maintain continuous output to all outlets as derived from the primary input
cable. If the primary power source becomes unstable or fails altogether, the ATS will switch over to the secondary power source until the primary input is
restored and stable. Super-fast switchover between primary and secondary power sources occurs within milliseconds. ATS functionality is supported by any
two compatible AC power sources, regardless of phase angle, to support a variety of advanced redundant power networking applications. Enables fault
tolerant hot-swappable UPS protection when used with a single UPS and fully redundant UPS protection when each cord is connected to a separate UPS
system. In a two-UPS environment, the primary input cable must be supported by a full time sine wave UPS with zero transfer time. Tripp Lite SmartOnline
series is highly recommended for use as the primary UPS in a two-UPS application. ATS configurations utilizing separate mains circuits, backup generators
and even separate utility power grid feeds are fully supported. On-board ATS processor constantly evaluates power quality on both input sources to prevent
transfer to the secondary source when unavailable or of lower quality than the primary source. Front input LED's display primary or secondary power
availability.
Features
200-240V 16/20A Automatic Transfer Switch (ATS) / Metered PDU (Agency de-rated to 16A continuous)
Provides a redundant power option for critical networking equipment with a single input power cord
2 digit display reports output power consumption in amps
1U horizontal rackmount form factor; 14.8 in. / 37.6 cm depth
10 outlets (8 C13, 2 C19)
Set of two C20 inlets support connection to separate PRIMARY and SECONDARY power sources
Two 12ft / 3.6m C19 to C20 power cables included
ATS circuits normally maintain output sourced from the primary input cable; As primary input power fails or becomes unstable, the ATS will switch to
maintain output sourced from the secondary input cable until power on the primary input is restored and stable
ATS configurations enable fault-tolerant, hot-swappable UPS protection when used with a single UPS and fully redundant UPS protection when each cord
is connected to a separate UPS system (in a two-UPS environment, the primary input cable must be supported by an online UPS with zero transfer time
1 / 4
similar to Tripp Lite SmartOnline series)
Advanced ATS configurations utilizing separate mains circuits, backup generators and even separate out of phase utility power grid feeds are fully
supported
On-board ATS processor constantly evaluates power quality on both inputs to prevent transfer to the secondary source when unavailable or of lower
quality than the primary source
Super-fast switchover between primary and secondary power sources occurs in 2-5 milliseconds
Built-in card slot supports optional SNMPWEBCARD or WEBCARDLX for permanent upgrade to a switched & monitored PDU system
Outlets are factory programmed for sequential turn-on at 250 millisecond intervals when the PDU is first energized to prevent inrush-related equipment
interaction on startup
Front panel LEDs confirm power availability on both input lines
Federal Trade Agreements Act / TAA Compliant for GSA Schedule purchases
Specifications
OVERVIEW
PDU Type Auto-Transfer Switch; Metered
OUTPUT
3.84kW (240V), 3.68kW (230V), 3.52kW (220V), 3.33kW (208V), 3.2kW (200V) / 16A total capacity; 16A max per
Output Capacity Details
C19 outlet; 12A (10A CE) max per C13 outlet
Frequency Compatibility 50 / 60 Hz
Output Receptacles (8) C13; (2) C19
Output Nominal Voltage 200; 208; 220; 230; 240
Overload Protection n/a
Adding SNMPWEBCARD or WEBCARDLX accessory offers upgrade path to switched PDU (only C13 outlets are
Customized Load Management switchable upon upgrade); Management Cards can also can be inserted temporarily as a configuration tool to
Receptacles custom program power-on and power-off C13 outlet sequences with user-specified time delays in response to loss
and restoration of primary input
INPUT
PDU Input Voltage 200; 208; 220; 230; 240
Recommended Electrical Service 20A 208/240V; 16A 230V
Maximum Input Amps 20
Maximum Input Amps Details Agency de-rated to 16A continuous
PDU Plug Type (2) IEC-320 C20
Input Cord Details Set of two inputs connect to separate PRIMARY and SECONDARY power sources
Input Cord Length (ft.) 12
Input Cord Length (m) 3.66
Input Phase Single-Phase
2 / 4